Lightning protection gives a strike a safe route from roof to ground, and it only works if every metre of that route is sound. Get a specialist to fit a new system, test the one you have, or put right what failed.

Find a contractor

Free to use: we suggest a specialist near you and tell you who before anything is shared.

Class
Front elevation of a building with a lightning protection systemA two-storey block 32 metres long and 12 metres high with a tower 8 metres wide and 24 metres high, drawn to scale. Dashed circles show the rolling sphere for the selected class resting against the building; copper dots mark where it touches, which is where strikes can land and air terminals are needed. Copper lines are down conductors at the typical spacing for the class, each ending in an earth electrode below ground.10 m
Rolling sphere
45 m radius
Roof mesh
15 m × 15 m
Down conductors
every 15 m
Full inspection
at least every 4 years, yearly for busy or sensitive buildings

Rolling sphereWhere it touchesConductors and earthsTest clamp

Drawn to scale: a 12 m block and a 24 m tower. Figures from BS EN 62305-3 Tables 2, 4 and E.2.

Four classes, one standard

BS EN 62305 is the British and European standard for lightning protection. A risk assessment under part 2 sets the level of protection a building needs, from Class I (the most demanding) to Class IV. The class fixes the rolling sphere, the roof mesh, how close the down conductors sit, and the longest a system can go between full inspections.

A typical office or school might come out at Class III: a 45 m sphere, a 15 m mesh and down conductors every 15 m. Switch classes on the drawing above to see what changes.

ClassSphere radiusRoof meshDown conductorsFull inspection
I20 m5 × 5 mevery 10 m2 years
II30 m10 × 10 mevery 10 m2 years
III45 m15 × 15 mevery 15 m4 years
IV60 m20 × 20 mevery 20 m4 years

Full inspection is the longest gap BS EN 62305-3 allows; it drops to one year for critical buildings such as offices, schools and places where many people gather. Most UK owners test every year anyway.

What lightning protection costs

Testing is priced by the size of the system and how long it takes on site. New systems and repairs are priced after a look at the building, so the clearest guides are diocesan figures and public contract values. All excluding VAT. A guide, not a quote.

Plan your costs

JobTypical figure
Annual test, house or small building£200 to £350
Annual test, small commercial or church£300 to £500
Annual test, school or large building£450 to £800
Inspection after a suspected strike£350 to £600
BS EN 62305 risk assessment£1,500 to £3,500
New system, small or average church£3,000 to £4,000
New system, primary school (public contract)£28,084
Surge protection, commercial intake£400 to £700
Where these figures come from

Test, risk assessment and surge figures from published UK contractor price guides, autumn 2026, firms not named. Church figures from Diocese of Chester guidance. The school install is Southend-on-Sea City Council’s award notice, August 2025. Read November 2026.

Buildings that need it most

Tall, isolated, full of people, full of electronics or simply old: these are the buildings where a lightning protection system earns its keep.

Does the law say you need it?

No UK regulation names lightning protection for ordinary buildings. The duty arrives another way. Employers and building owners must assess the risks to people and act on them, and electrical systems, which lightning protection is treated as, must be kept in a safe condition. If a BS EN 62305 risk assessment shows a building needs protection, it needs to be fitted and maintained.

In practice the push usually comes from an insurer, a diocese, a trust estates team or a fire risk assessor. Read the regulations in full.

How the job gets done

  1. Look at what is there

    A specialist reads the last certificate and drawing, then inspects and tests the system, or assesses the building if there is none.

  2. Price it

    A test fee, a repair schedule tied to the defects, or a design and quote for a new system to the right class.

  3. Do the work

    Earths, down conductors and roof conductors fitted or repaired, with access arranged and consents in place on listed buildings.

  4. Certify and diary

    Readings recorded on a certificate, the drawing updated, and the next test booked for 11 to 12 months ahead.

Questions about lightning protection

What is lightning protection?

A system that gives a lightning strike a safe, planned path to earth. Metal on the roof catches the strike, down conductors carry it down the outside of the building, and earth electrodes spread it into the ground. Surge protection devices then protect the wiring and equipment inside.

Is lightning protection a legal requirement in the UK?

Not by name for most buildings. Duty holders must assess risks under the Management of Health and Safety at Work Regulations and keep electrical systems safe under the Electricity at Work Regulations 1989. A BS EN 62305 risk assessment shows whether a building needs protection, and insurers often make it a condition. See lightning protection regulations.

How often should lightning protection be tested?

In practice, every 11 to 12 months. BS EN 62305-3 sets maximum gaps by class, as short as one year for buildings with sensitive systems or many people inside, and the DfE says schools should test at least annually.

How much does lightning protection cost?

Testing runs from £200 to £350 for a small building to £450 to £800 for a school, from published UK contractor price guides, autumn 2026. A new system for a small church is around £3,000 to £4,000 on diocesan guidance, and two recent public installs were published at £27,000 and £28,084. Use the cost planner.

What is the difference between a lightning conductor and surge protection?

A lightning conductor protects the structure and the people in it from a direct strike. Surge protection protects electrical and electronic equipment from the voltage spikes a strike on or near the building sends along cables. A complete design under BS EN 62305 includes both.

Who installs and tests lightning protection?

Specialist lightning protection contractors, many of them members of ATLAS, the Association of Technical Lightning and Access Specialists. Insurers and dioceses often ask for a member. Surge protection devices are usually fitted by an electrical contractor working to BS 7671.

Find a lightning protection contractor

Three quick screens: the postcode of the building, the work, then your contact details. Most people finish in about two minutes.

We are an introduction service, not a lightning protection contractor. We tell you which specialist covers your building before anything is shared, and no one calls you unless you agree.